© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
BC06EXT_DBL_LST_EN_0826.PDF • PAGE 3
ABuilding Safety. Building Security.
By means of the Extinguishing Board EXB1-1, the
Fire/Extinguishing Control Panels BC06-1EXT and
BC06-2EXT provide numerous inputs and outputs with
xed or parameterisable function. With that, the follo-
wing components of an extinguishing system can be ac-
tuated and monitored in accordance with EN 12094-1:
Activation devices for the manual activation of the
ooding process
Emergency hold devices for the manual delay of the
ooding process
Emergency abort devices for aborting the ooding
process
Fault detection devices for monitoring the compon-
ents of the extinguishing system
A disable device for the indication of the mechanical
blocking of the extinguishing agent‘s network
A ooding switch that indicates the ow of the extin-
guishing agent
A device for switching to the manual mode for ex-
ample, a key switch
Signalling devices for indicating the activated conditi-
on and the released condition
The control device for activating the ooding for
example, a solenoid valve
Auxiliary outputs for actuating aps or for turning off
devices and systems
Extinguishing control
The operating fi eld of the Fire/Extinguishing Control Pa-
nels BC06-1EXT and BC06-2EXT provides 13 LEDs for
displaying the operating conditions and 4 buttons for
the operation of the extinguishing system.
The LEDs indicate the following operating conditions:
Pre-activation/activation of the extinguishing module
Released condition of the extinguishing output
Extinguishing output fault
Extinguishing module fault/disablement
Extinguishing medium fault/fault of the fault input
Emergency hold/emergency hold device fault
Activation device fault/disablement
Signal output activated/signal output faulty/disabled
Manual mode of the extinguishing module
Fault of the activated condition output
The buttons on the operating eld have the following
functions:
Disable/enable the extinguishing module
Start/terminate the manual mode
Disable/enable the activation devices
Disable/enable the signal output
Display and operating elements